Appendix
If it's P group parameter, changing high-order F of the function code address to be 0 can realize the
function. If it's A group parameter, changing high-order A of the function code address to be 4 can realize
the function. Corresponding function code address is expressed as below: high-order byte: 00~0F (P
group), 40~4F (A group); low-order byte: 00~FF
E.g.: function code P3-12 is not stored in EEPROM, the address is expressed as 030C; function code
A0-05 is not stored in EEPROM, the address is expressed as 4005; the address can only write RAM and
conduct read action. When reading, it's invalid address. For all parameters, CMD code 07H can also be
used to realize the function.
When the frequency convertor is in running status, some parameters can't be modified. Some
parameters can't be modified no matter what is the status of frequency convertor. When modifying the
function code parameters, range, unit and related descriptions of parameters should be also noticed.
Halt/running parameters:
Parameter address
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
100A
100B
100C
100D
100E
100F
1010
1011
1012
1013
1014
1015
1016
1017
Specification of high-performance vector convertor
Parameter description
*Communication setting value (-10000~10000) (decimal system)
Running frequency
Busbar voltage
Output voltage
Output current
Output power
Output torque
Running speed
DI input mark
DO output mark
AI1 voltage
AI2 voltage
AI3 voltage
Count value input
Length value input
Loading speed
PID setting
PID feedback
PLC step
PULSE frequency, unit 0.01kHz
Feedback speed, unit 0.1Hz
Surplus running time
AI1 voltage before calibration
AI2 voltage before calibration