Specification of high-performance vector convertor
Switching mode is as follows:
The current way for function parameters, switch to a custom parameters
4.4 user customization parameters
The establishment of the user's customized menu is mainly to facilitate users to view and modify the
commonly used functional parameters.The parameters of customized menu display in the form of "uP3-02",
it is said that the function of parameter P3-02 in the custom menu to modify the parameters and modify the
parameters of the effect of the corresponding programming in general condition is the same.
User customized menu function parameters from the PE group, by the PE group to select the functional
parameters, set to P0-00 is not selected
Choose, can be set to 30; if the menu when the display "NULL", which means that the user to customize
the menu.
When the initial user custom menu has been deposited in the
commonly used 16 parameters to facilitate the user to use:
P0-01: control mode
P0-03: dominant frequency source selection
P0-08: preset frequency
P0-18: deceleration time
P3-01: torque boost
P4-01:DI2 terminal function selection P4-02:DI3 terminal function selection
P5-04:DO1 output selection
P6-00: start mode
Users can according to their own specific needs to be
customized for the user to edit.
4.5 Method for viewing state parameter
Under the outage or running state , Through the shift key"
parameter, respectively.By the function code P7-03 (running parameters 1), P7-04 (operation parameters
(2), P7-05 (parameters) downtime by binary bit choose whether to display the parameters.
In stop state, with a total of 16 parameters can choose whether show stop condition respectively: set
frequency, bus electric pressure, DI input state, the DO output state, voltage analog input AI1, AI2 analog
input voltage, the analog input voltage AI3, actual count value, the actual length value, PLC operation step,
load speed display, PID setting, PULSE input PULSE frequency and three reserve parameters, switch input
sequences show that the selected parameters.
In running state, the running state of the five parameters:Operating frequency, set frequency,
busbar voltage, output voltage, output current for the default display, other display parameters:Output
power, output torque, DI input state, the DO output state, voltage analog input AI1, AI2 analog input
voltage, the analog input voltage AI3, actual count value, the actual length value, linear velocity, PID,
PID feedback is displayed by the function code P7-03, P7-04 bitwise (converted to binary) selection,
switch input sequences show that the selected parameters.
Inverter power again to electricity, the display parameter is the default for inverter power lost
before the choice of parameters.
P0
P0-02: command source selection
P0-07: frequency source selection
P0-17: acceleration time
P3-00:V/F curve setting
P4-00:DI1 terminal function selection
P5-07:AO1 output selection
P6-10: stop mode
The keys
ENTER
-USEr
uP0-01
The
keyboard
display
- 37 -
Operation and display
"Can display a variety of state