Specification of high-performance vector convertor
VF slip compensation gain Factory default
P3-09
Setting range
VF Slip compensation. It can be compensated induction motor generated when the load increases the
motor speed deviation when the load changes the motor speed can be stable.
VF Slip compensation gain is set to 100.0%, indicating that slip when the motor with a rated load
compensation to the motor rated slip. But the motor rated slip, the drive motor rated frequency group by
P1 and rated speed to get own calculations.
Adjust VF rpm slip compensation gain, generally when the rated load, the motor speed and the target
speed is substantially the same as the principle. When the motor speed and the target value is not the same,
you need to be properly fine-tune the gain.
VF over excitation gain
P3-10
Setting range
During the deceleration, the over-excitation control bus voltage rise can be suppressed to avoid
overvoltage fault. Greater the over excitation gains, stronger the suppression has effect.
For conditions that in the inverter deceleration process, it is easier to be over-pressured and sounds
alarm, you need to improve the over excitation gain. But if excitation gain is too large, easily lead the
output current to increase; you need to weigh in the application.
For the case of small inertia, deceleration of the motor voltage rise does not appear, it is
recommended that the over excitation gain is 0; For braking resistance occasion, it is also suggested that
over-excitation gain is set to 0.
Voltage % Vb
V1-V3: Multi-speed V / F voltage percentage of segment 1-3
F1-F3: Multi-speed V / F frequency percentage of segment 1-3
Vb: Motor rated voltage Fb: motor rated operating frequency
0%~200.0%
Factory default
0~200
V3
V2
V1
F2
Figure 6-4 Diagram of multi-point V / F curve setting
F3
Fb