Specification of high-performance vector convertor
Terminal command mode
Setting
P4-11
range
This parameter defines the external terminal through the inverter to control the operation of four different ways.
0: Two-wire mode 1: This mode is the most commonly used two-line mode. By the terminal DI1, DI2 to determine
the motor forward and reverse operation.
Terminal function set as follows:
Terminals
Wherein, DI1, DI2 are multi-function input terminal of DI1 ~ DI10, the level is effective.
1: Two-wire mode 2: Use this mode when DI1 terminal function operation enable terminal and DI2 terminal function
to determine the direction.
Terminal function set as follows:
Where in, DI1, DI2 are multi-function input terminal of DI1 ~ DI10, the level is effective.
0
Two-wire 1
1
Two-wire 2
2
Three-wire 1
3
Three-wire 2
DI1
DI2
Figure 6-6 Two-line mode 1
Terminals
DI1
DI2
Figure 6-7 Two-line mode 2
Factory default
Set point
1
Forward running (FWD)
2
Reverse running (REV)
VFD
Set point
1
Forward running (FWD)
2
Reverse running (REV)
VFD
- 89 -
Parameter description
0
Description
Description