Specification of high-performance vector convertor
P9-59
Setting range
Momentary power failure deceleration frequency
P9-60
Setting range
Instantaneous power voltage recovery judgment
P9-61
Setting range
Instantaneous stop non-stop action judgment
P9-62
Setting range
This feature means that in an instant power failure or a sudden drop in voltage, the inverter by reducing the output speed,
back to reduce the load energy compensation inverter DC bus voltage to maintain the drive continues to run.
If P9-59 = 1, the instantaneous power failure or a sudden drop in voltage, the inverter deceleration, when the bus voltage is
restored, the drive accelerates to the set frequency normal operation. Analyzing the bus voltage returns to normal is based on
the normal bus voltage P9-61 and lasts longer than the set time
If P9-59 = 2, the instantaneous power failure or a sudden drop in voltage, the inverter will decelerate to a stop
busbar voltage
Instantaneous power
failure action to determine
the voltage P9-62
Operating frequency
Instantaneous power cut
deceleration frequency
switching point P9-60
Operating frequency
Instantaneous power cut deceleration
frequency switching point P9-60
Instantaneous stop action selection
0
1
2
switching point
time
voltage
Deceleration time 3
Deceleration time 3
Figure 6-24 Schematic diagram of instantaneous power failure
Factory default
Factory default
0.0%~100.0%
Factory default
0.00s~100.00s
Factory default
60.0%~100.0% (standard bus voltage)
Instantaneous stop electric
voltage recovery judgment
瞬时停电动电压
回升判断时间
time P9-61
P9-61
Deceleration time 4
Pick up time
(P9-59=2: gear down)
Deceleration time 4
- 122 -
Parameter description
0
Invalid
Slow down
Slowdown stop
0.0%
0.50s
80.0%
(P9-59=1: slow down)
time