Specification of high-performance vector convertor
Code
Fault protection action selection
P9-49
3
Fault protection action selection
P9-50
4
Continue to run frequency
P9-54
selection when fault happens
Abnormal alternative frequency 60.0%~100.0% (100.0% Corresponding to
P9-55
Motor temperature sensor type
P9-56
Motor overheating protection
P9-57
threshold
Motor overheating prediction
P9-58
alert threshold
Instantaneous power failure
P9-59
action selection
Retention
P9-60
Instantaneous power voltage
P9-61
recovery judgment time
Instant power cut action judging
P9-62
voltage
Load missing protection selection 0: invalid
P9-63
Load missing detection level
P9-64
Name
Bit: User-defined fault 1 (27)
0: Free halt
1: Stop according to stop mode
2: Continue to run
Hundred bit: Power-on time is reached (29)
Thousand bit: Carrying out (30)
0: Free halt
1: Deceleration to stop
2: Decelerated to 7% of the rated motor
frequency continues to run, When you can
not afford to load automatically restored to
the set frequency operation
Ten thousand bit: Runtime PID feedback
loss (31)
0: Free halt
1: Stop according to stop mode
2: Continue to run
Bit: Excessive speed deviation (42)
0: Free halt
1: Stop according to stop mode
2: Continue to run
Ten bit: Super speed motor (43)
Hundred bit: The initial position error (51)
0: In the current operating frequency
operation
1: Run at set frequency
2: Run at upper limit frequency
3: Lower limit frequency operation
4: Alternate abnormal frequency operation
the maximum frequencyP0-10)
0: no temperature sensor
1: PT100
2: PT1000
0℃~200℃
0℃~200℃
0: invalid
1: deceleration
2: deceleration to halt
P9-62~100.0%
0.00s~100.00s
60.0%~100.0% (standard busbar voltage)
1: valid
0.0~100.0%
Setting range
- 54 -
Functional parameter table
Default
Change
00000
00000
0
100.0%
0
110℃
90℃
0
100.0%
0.50s
80.0%
0
10.0%