Parameter description
Set point
Function
16
AI1>AI2
17
Upper limit frequency arrival
The lower limit frequency
18
arrival (not output shutdown)
19
Brown-state output
20
Communication Preferences
21
Retention
22
Retention
Zero-speed operation 2
23
(shutdown also output)
Cumulative power-up time
24
arrival
25
Frequency level detection
output FDT2
Frequency 1 reaches the output Please refer to the function code P8-30, P8-31 description.
26
Frequency 2 reaches the output Please refer to the function code P8-32, P8-33 description.
27
Current 1 reaches the output
28
Current 2 reaches the output
29
The timing to the output
30
AI1 input overrun
31
Carrying out
32
Reverse operation
33
Zero current state
34
Module temperature reached
35
Software current limit
36
The lower limit frequency
37
arrival (also stop output)
Alarm output
38
Motor overtemperature alarm
39
The running time arrival
40
Specification of high-performance vector convertor
When the value is greater than the analog input AI1 value AI2 input and
output ON signal.
When the operation frequency reaches the upper limit frequency, output
ON signal.
When the operation frequency reaches the lower limit frequency, output
ON signal. Under the standstill signal is OFF.
When the inverter is under voltage state, output ON signal.
Refer to the communication protocol.
Retention
Retention
Inverter output frequency is 0, the output ON signal. The signal is also at a
standstill is ON.
When the inverter's accumulated power-on time (P7-13) P8-16 exceeds the
set time, the output signal is ON.
Please refer to the function code P8-28, P8-29 description.
Please refer to the function code P8-38, P8-39 description.
Please refer to the function code P8-40, P8-41 description.
When the timer function Select (P8-42) is valid, the inverter running time
after this set timing, output ON signal.
When the value is greater than the analog input AI1 P8-46 (AI1 input
protection limit) or less than P8-45 (AI1 input protection limit), it outputs
ON signal.
When the drive is off-load state, output ON signal.
Reverse drive is running, output signal ON
Please refer to the function code P8-28, P8-29 description.
Heat sink temperature of the inverter module (P7-07) to reach the set
temperature reaches the value of the module (P8-47), the output signal ON
Please refer to the function code P8-36, P8-37 description.
When the operation frequency reaches the lower limit frequency, output
ON signal. In the stop state of the signal is also ON.
When the inverter failure, and the failure to continue processing mode, the
inverter alarm output.
When the motor temperature reaches P9-58 (motor overheating prediction
threshold), the output signal is ON. (motor temperature can be viewed
through U0-34)
The inverter starts running longer than the time set by P8-53,
output ON signal.
- 96 -
Explanation