Specification of high-performance vector convertor
P8-38
Any arrival current width 1
P8-39
P8-40
Any arrival current width 2
P8-41
When the output current of the inverter, setting the current reach any positive or negative detection width, the inverter
output multifunction DO ON signal.
VFD provides two sets of current and any arrival detection width parameter, a functional schematic diagram in Figure 6-23.
Arbitrary
arrival current
Random arrival current
detection signal DO or relay
Timing function selection
P8-42
Setting range
Timed Run time selection
P8-43
Setting range
P8-44
The set of parameters used to complete the drive timing running function.
When P8-42 timing function selection is valid, the inverter starts the beginning of time, after reaching set the timer run time,
the inverter automatically shut down, while multi-function DO output ON signal.
Any arrival current 1
Setting range
Setting range
Any arrival current 2
Setting range
Setting range
Output current
ON
OFF
Figure 6-23 Schematic diagram of
any arrival current detection
0
1
0
1
2
3
Timed Run Time
Setting range
Factory default
0.0%~300.0% (motor rated current)
Factory default
0.0%~300.0% (motor rated current)
Factory default
0.0%~300.0% (motor rated current)
Factory default
0.0%~300.0% (motor rated current)
ON
ON
OFF
Factory default
Factory default
Analog Input Range 100% correspond to P8-44
Factory default
0.0Min~6500.0Min
- 115 -
Parameter description
100.0%
0.0%
100.0%
0.0%
Arbitrary reach
current width
time
OFF
0
Invalid
Valid
0
Setting P8-44
AI1
AI2
AI3
0.0Min