Specification of high-performance vector convertor
FM terminal is a programmable multiplexing terminal can be used as high-speed pulse output terminal (FMP), the
switch can also be used as open collector output terminal (FMR).
As the pulse output FMP, the maximum output pulse frequency is 100kHz, FMP-related functions can be found P5-06
instructions.
P5-01
FMRI function selection (open collector output terminal)
P5-02
Relay output function selection (T / A-T / B-T / C)
P5-03
Expansion card relay output function selection (P / A-P / B-P / C)
P5-04
DO1 output function selection (open collector output terminal)
P5-05
Expansion card DO2 output function selection
The five function code is used to select the five digital outputs function, where T / A-T / B-T / C and P / A-P / B-P / C,
respectively on control board and expansion card relay.
Multi-function output terminal functions are as follows:
Set point
Function
No output
0
Inverter running
1
Fault output (downtime)
2
3
Frequency level detection
output FDT1
Frequency arrival
4
Zero speed operation (no output
5
shutdown)
Motor overload pre-alarm
6
Inverter overload pre-alarm
7
Set counting value arrival
8
Designated counting value
9
arrival
Length arrival
10
PLC Complete cycle
11
Total running time arrival
12
Frequency is defined in
13
Torque limiting
14
Ready to run
15
Explanation
Output terminal has no function
Indicates the drive is in running state, the output frequency (can be zero),
ON signal is output.
When the drive fails and downtime, it outputs ON signal.
Please refer to the function code P8-19, P8-20 description.
Please refer to the function code P8-21 description.
Inverter running and the output frequency is 0, output ON signal. When
the drive is shut down, the signal is OFF.
Before the motor overload protection, according to the overload pre-
alarm threshold value judgment over pre-alarm threshold value output
ON signal. Motor overload parameter settings see Function Code P9-00
~ P9-02.
Before the inverter overload occurs 10s, output ON signal.
When the count value reaches the value of PB-08 set, output ON signal.
When the count value reaches the value of PB-09 group,
output ON signal. PB reference counting function group
Function
When detecting the actual length exceeds PB-05 set length, output ON
signal.
After simple PLC completes one cycle, the output of a pulse width of
250ms.
When the accumulated running time exceeds the time set by P8-17, output
ON signal.
When the set frequency exceeds the upper limit frequency or lower
frequency, and output frequency has reached the upper limit frequency
or lower frequency, the output ON signal.
Drive under the speed control mode, when the output torque reaches
the torque limit, the inverter is in the stall protection status, and ON
signal is output.
When the inverter main circuit and control circuit power supply has
stabilized, and the drive does not detect any fault information, the drive
is in an operational state, output ON signal.
- 95 -
Parameter description
Factory default
0
Factory default
2
0
Factory default
Factory default
1
Factory default
4