Parameter description
DC injection braking initial frequency
P6-11
Halt DC braking waiting time
P6-12
P6-13
P6-14
DC injection braking Starting frequency: deceleration stop process, when the operating frequency to reduce the frequency to
start DC braking process.
DC braking waiting time: the operating frequency is reduced to DC braking starting frequency, the inverter will stop output
for some time before starting DC braking process. At high speed to prevent the start of DC braking can cause over-current
fault.
DC braking current: DC braking means the output current, the relative percentage of the motor rated current. The higher this
value, the DC brake effect, but the greater the heat the motor and the inverter.
DC braking time: DC braking holding time. This value is 0 DC braking process is canceled. DC injection braking process
schematic diagram shown in Figure 6-13.
Setting range
Setting range
Halt DC braking current
Setting range
Halt DC braking time
Setting range
Specification of high-performance vector convertor
Factory default
0.00Hz ~ maximum frequency
Factory default
Factory default
Factory default
- 102 -
0.00Hz
0.0s
0.0s~36.0s
0%
0%~100%
0.0s
0.0s~36.0s