Specification of high-performance vector convertor
Type
Terminal
symbol
DI1- OP
DI2- OP
Digital
DI3- OP
input
DI4- OP
DI5- OP
Analog
output
AO1-GND
DO1-CME
Digital
output
FM- CME
T/A-T/B
Relay
T/A-T/C
output
3) Functional description of jumper and auxiliary terminals
Terminal name
Digital input 1
1. Optical coupling isolation, be compatible with bipolar input
Digital input 2
2. Input impedance: 2.4kΩ
Digital input 3
3. Voltage range for level input: 9V~30V
Digital input 4
High-speed impulse
Apart from features of DI1~DI4, it can be high-speed impulse
input terminal
input channel. Max. input frequency: 100kHz
J5 jumper on control panel decides voltage or current output.
Output voltage range: 0V~10V
Analog output 1
Output current range:0mA~20mA
Optical coupling isolation, bipolar open collector output
Output voltage range: 0V~24V; output current range: 0mA~50mA
Caution: digital output CME and digital input COM are internally
Digital output 1
isolated, but short circuit of CME and COM is realized through
J10 jumper on control panel (DO1 is +24V drive by default). If
DO1 needs to be drived by external power, pull out J10 jumper
Be restricted by function code F5-00 "output way selection of FM
High-speed
terminal"
impulse output
As high-speed impulse output, max. frequency is 100kHz
As open-collector output, it's the same with DO1 specification
Drive capability of contact:
Normally closed terminal
AC250V, 3A, COSø=0.4
Normally open terminal
DC 30V, 1A
Figure 3-6 Location diagram of jumper and auxiliary terminals
Mechanical and electrical installation
Functional
description
- 30 -

Publicité