Specification of high-performance vector convertor
P3-14
VF separation rise time refers to the output voltage changes from 0V to rated motor voltage required
time. Shown in Figure 6-5:
Output voltage
Motor rated voltage
Output voltage target value
Actual voltage rise time
P4 group: Input termianl
This series inverter comes standard with five multifunctional digital input terminals (Where DI5 can
be used as high-speed pulse input terminal). Two analog input terminals. If the system needs more
input and output terminals can be optional multifunctional input and output expansion card.
Multi-function input and output expansion card has five multifunctional digital input terminals
(DI6~DI10), An analog input terminal (AI3).
P4-00
DI1Terminal function selection Factory default
P4-01
DI2Terminal function selection Factory default
P4-02
DI3Terminal function selection Factory default
P4-03
DI4Terminal function selection Factory default
P4-04
DI5Terminal function selection Factory default
P4-05
DI6Terminal function selection Factory default
P4-06
DI7Terminal function selection Factory default
P4-07
DI8Terminal function selection Factory default
P4-08
DI9Terminal function selection Factory default
P4-09
DI10Terminal function selection Factory default
These parameters are used to set the digital multi-function input terminal functions can be selected
functions as follows:
VF isolated voltage rise time
Setting range
V
Set the voltage rise time
Figure 6-5 Diagram of V/F separation
Factory default
0.0s~1000.0s
Set voltage fall time
1 (running)
4 (positive turning point move)
9 (fault reset)
12 (multi speed 1)
13 (multi speed 2)
0
0
0
0
0
- 85 -
Parameter description
0.0s
Time t
Actual voltage fall time