Télécharger Imprimer la page

MSW Motor Technics MSW-FI-7500 Manuel D'utilisation page 235

Publicité

Parameter description
2: Three-wire control mode 1: This mode is enabled terminal DI3, respectively, by direction DI1, DI2
control.
When there is the need to run, the terminal must first DI 3 closed by the rising edges of the DI1 or DI2 to achieve
forward or reverse motor control.
When you need to stop, by disconnecting DI3 terminal shall signal to achieve. Wherein, DI1, DI2, DI3 are
multifunctional input terminals of DI1 ~ DI10, DI1, DI2 pulse are effective, DI3 is effective level.
Among:
SB1: stop button
3: Three-line control mode 2: This mode enable terminal to DI 3, run the command given by the DI1,
DI2 direction by the state to decide.
Terminal function is set as follows:
In the need to run, must first close the DI3 terminal, from the DI1 of the pulse rise along the
motor running signal, DI2 state of the motor direction signal.
In the need to stop, it is required to disconnect the DI3 terminal signal to achieve. Among them,
DI1, DI2, DI3 for the DI1 ~ DI10 multi function input terminals, DI1 for the pulse effective, DI3, DI2
is effective.
Terminals
DI1
DI2
DI3
SB2
SB1
SB3
Figure 6-8 Three wire control mode 1
SB2: Forward button SB3: reverse button
Terminals
DI1
DI2
DI3
Running direction
K
Forward
0
REV
1
Figure 6-9 Three wire control mode 2
Specification of high-performance vector convertor
Set point
1
2
3
VFD
Forward running (FWD)
DI1
DI3 Three line operation
control
DI2 Reverse run (REV)
COM Digital public end
Set point
1
2
3
SB2
DI1
SB1
DI3 Three line operation control
K
DI2
- 90 -
Description
Forward running (FWD)
Reverse running (REV)
Three-wire run control
Description
Forward running
Reverse running (REV)
Three-wire run control
VFD
Forward running (FWD)
Reverse run(REV)
COM digital public end

Publicité

loading