Télécharger Imprimer la page

MSW Motor Technics MSW-FI-7500 Manuel D'utilisation page 173

Publicité

Specification of high-performance vector convertor
d)
Connection terminal P1, (+) of external DC reactor
For the frequency convertor at above 220V37KW and 380V75kW, connection strap between P1
and (+) terminals needs to be removed when installing DC reactor externally, and connect DC
reactor between two terminals.
e)
U, V, W on output side of frequency convertor: output side of frequency convertor shall not
connect capacitor or surge absorber, otherwise it will lead to frequent protection and even damage
of convertor. Due to influence of distributed capacitance, if motor cable is too long, electric
resonance will produce easily, which will damage motor insulation or produce large leak current
and frequent protection of convertor. If motor cable is >100m, AC input reactor should be installed.
f)
Earthing terminal PE\
For different models, the marking of earthing terminal may be different, but the meaning is same. In
above descriptions,
Keep reliable earthing of earthing terminal and resistance value of ground wire should be <0.1Ω,
otherwise it will lead to abnormal operation and even damage of device. Do not use earthing terminal
PE or
and N terminal on null line of power in common.
3.2.5 Control terminal and wiring
1) Layout diagram of terminals on control circuit is as below:
(Note: there's no short-circuit strap between CME and COM, OP and +24V of frequency
convertor. Users select wiring way of CME and OP respectively through J10, J9)
2) Functional descriptions of control terminals
Figure 3-3 Functional descriptions of control terminals of frequencyc convertor
Type
Terminal
symbol
+10V-GND
Power
+24V-COM
OP
AI1-GND
Analog
input
AI2-GND
means that earthing marking is PE or
Figure 3-5 Layout diagram of terminals on control circuit
Terminal name
Offer +10V power externally, max. output current: 10mA
Connect+10V
Be commonly used as working power of external potentiometer,
power externally
resistance value range of potentiometer : 1kΩ~5kΩ
Offer +24V power externally, be used as working power of digital
Connect+24V
input/output terminal and power of external sensor
power externally
Max. output current: 200mA
Connect +24V or COM through J9 jumper on control panel.
If using external signal to drive DI1~DI5, OP needs to connect
Input terminal of
with external power, and pull out J9 jumper
external power
1. Range of input voltage: DC 0V~10V
Analog input
2. Input impedance: 22kΩ
terminal 1
1. Input range: DC 0V~10V/4mA~20mA, depend on J8 jumper on
Analog input
control panel
terminal 2
2. Input impedance: 22kΩ for voltage input, 500Ω for current input
Mechanical and electrical installation
.