90
AVENTICS | CANopen | R402003660–BAL–001–AE
Replacement
One-time error caused
by hardware
One-time error caused
by firmware
When starting the bus coupler (power on), the hardware
components are tested. If an error is found, the system is
stopped (set to system stop mode).
Plausibility tests are constantly carried out while the firmware
is running. If an error is detected during these tests, the "system
stop" mode is activated.
7.5.1
Exiting system stop
Restart the module by disconnecting and then reconnecting
the power supply (power on).
8
Replacement
A faulty bus coupler may have to be replaced with a new bus
coupler. You may also replace a multipole connector or another
bus coupler of a CL03/CL03-XLVS with a bus coupler.
The warranty from AVENTICS only applies to the delivered
configuration and extensions that have been taken into
account in the configuration. The warranty no longer
applies after a conversion that exceeds these extensions.
8.1
Replacing a bus coupler
Applied electric voltage and high pressure
Danger of injury from electric shock and sudden pressure drops.
Make sure the system is not under pressure or connected
to power when you exchange a module.
WARNING