110
AVENTICS | CANopen | R402003660–BAL–001–AE
Appendix – bus master configuration
Parameter data length
Parameter data
Table 29:
Coding of the diagnosis bytes
Byte
Meaning
Bit 0
0
No diagnosis
1
Faulty valve supply fuse or digital output (collective bit)
Bit 1
0
No diagnosis
1
Low load supply voltage U
Bit 2
0
No diagnosis
1
Low load supply voltage U
Bit 3
0
No diagnosis
1
Load supply U
Bit 4
0
No diagnosis
1
Load supply U
Bit 5
0
No diagnosis
1
Bit 6
0
No diagnosis
1
Bit 7
0
No diagnosis
1
1)
Approx. 110 ms after switched on, approx. 120 ms after switched off
13.7.4
Parameter information
The bus coupler is configured via index 2040 of the OD.
Index 2040 subindex 0 contains the highest subindex
Highest subindex = 2
Index 2040 subindex 1 supplies the number of parameterization
data: number = 1
Index 2040 subindex 2
The parameterization data can be written in and the diagnosis
can therefore be switched on or off.
1)
Q1
1
Q2
missing
Q1
missing
Q2