Commissioning and operation
S1
S2
7.1.1
Setting the data rate
Set the data rate (baud rate) with the switches S3.1 to S3.3
in accordance with the information listed in Table 8 below.
Default setting: 1 Mbit/s
Table 8:
Switch assignment for data rate setting
Data rate
Max. wire length
1 Mbit/s
25 m
Reserved
500 kbit/s
100 m
250 kbit/s
250 m
125 kbit/s
500 m
50 kbit/s
1 km
20 kbit/s
2.5 km
10 kbit/s
5 km
7.1.2
Setting the bus coupler address
The station address is set using switches S1 and S2.
Changes during operation
Changes to the addressing are only activated after a power
reset.
Never change the settings during operation.
Turn the device off before changing the address setting.
Assign the station address freely from 1 to 99 using S1 and S2.
– S1: Unit digits from 0 to 9
– S2: Tens digits from 0 to 9
– [S2] [S1] = Station address
Default setting: node ID = 02
Do not use address 0, it causes a system stop.
S3.3
ON
ON
ON
ON
OFF
OFF
OFF
OFF