88
AVENTICS | CANopen | R402003660–BAL–001–AE
Commissioning and operation
Table 13:
Definitions for diagnostic LEDs on the bus coupler
LED
Signal
Off
ERR
Off
Red
Flashes red+
Flashes red~~
Flashes red++
Flashes red+++
1)
This display appears only as long as the overloaded output is controlled or as long as the total current
of the valve supply is exceeded.
2)
Flashes green~
3)
Flashes red~~/flashes green~~
4)
Flashes red+/flashes green+
5)
Flashes red++
6) Flashes red+++
Description
Module is in an "initializing" state.
No bus error recognized
Module is in "bus off" state (not active in CAN).
4)
Module is in "error passive" state (at least one error counter has
reached or exceeded the maximum value).
3)
Module is in "auto baud rate detection or LSS services" state
(the RUN LED alternatively flashes as well).
Invalid node ID (node ID = 0 is not permitted) (see „System stop"
on page 89).
5)
Module is in "error control event" state.
A heartbeat/monitoring event has occurred.
Condition: Object 1006 supported.
6)
Module is in a "sync error" state. SYNC message was not sent within
configured time.
Slow flashing of the display: 0.2 s on/0.2 s off
Fast flashing of the display: 0.05 s on/0.05 s off
Flashing of the display: 0.2 s on/1 s off
2x flashing: 0.2 s on/0.2 s off; 0.2 s on/1 s off
3x flashing: 0.2 s on/0.2 s off; 0.2 s on/0.2 s off; 0.2 s on/1 s2off
7.4
Commissioning the VS with a bus coupler
Before commissioning the system, the following steps must
have been carried out and completed:
You have assembled the valve system and the bus coupler
(see "Assembling the CL03/CL03-XL with bus coupler" on
page 74).
You have assembled the bus coupler (see "Connecting the
bus coupler electrically" on page 76).
You have made the settings and configured the system (see
"Making settings" on page 81).
You have configured the bus master so that it controls the
valves correctly.