78
AVENTICS | CANopen | R402003660–BAL–001–AE
Assembly
POWER
X10
BUS IN
X71
BUS OUT
X72
POWER
X10
BUS IN
X71
BUS OUT
X72
6.3.2
1. If you do not use pre-assembled wiring, connect the plugs
according to Table 5.
2. Connect the incoming bus connection to the X71 input (1).
3. Connect the outgoing bus cable with the next module using
the X72 output (2).
4. Ensure that the plug housing is securely fitted to the bus
coupler housing.
1
2
6.3.3
1. If you do not use pre-assembled wiring, connect the plugs
according to Table 5 on page 77.
2. Connect the incoming bus connection to the X71 input (1).
3. Close off the X72 socket (2) with a termination plug (see
chapter "Spare parts and accessories" on page 96).
4. Ensure that the plug housing is securely fitted to the bus
coupler housing.
1
2
A potential equalization line of at least 10 mm
between the devices to avoid compensating currents from
flowing over the shield of the bus cable.
Connecting the bus coupler as an intermediate
station

Connecting the bus coupler as a final station

2
is needed

Publicité