Encoder Transmit Outputs – AC30D ONLY
ENCT-A (X33/01), ENCT-/A (X33/02), ENCT-B (X33/03), ENCT-/B (X33/04), ENCT-Z (X33/05), ENCT-/Z (X33/06)
Signaling Type
Output Voltage
Levels
Rated Output Current
Maximum Count
Frequency
Operating Modes
Propagation Delay
in Repeat Mode
Protection
Variateur de vitesse de la série AC30
Differential: A to /A, B to /B and Z to /Z
Selectable:
Off-load nominal output (differential) voltages: 5V, 12V, 15V or 20V
Rated-load nominal output (differential) voltages: 4.0V, 10.8V, 13.9V or 18.9V (respectively)
33mA
(100mA total for all three outputs combined)
250kHz pulse rate
Selectable:
Repeat of Encoder Input 1
Repeat of Encoder Input 2
Synthetic encoder output
Digital outputs (general purpose)
< 1μs
Short-circuit protected.