D-168
Parameter Reference
Parameter Name
No.
Comms Control Word
0627
Control Word from Fieldbus.
Control Word
0644
Monitor (read-only) Control Word updated from the active source.
Path
Parameters::Motor Control::Sequencing
Parameters::Motor Control::Sequencing
Default
Range
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
Units
Writable
ALWAYS
NEVER
AC30 series Variable Speed Drive