Local Control
Parameters::Keypad::Local Control
These parameters configure the use of the GKP keys for local start / stop control of the drive.
Parameter Name
No.
Run Key Action
1140
Defines the use of the green run key in local mode.
When RUN is selected, pressing the green Run key will start the drive using Local Reference as the active setpoint. To stop the drive
press the RED Stop key.
When JOG is selected, pressing the green Run key will start the drive running using the Jog Setpoint as the active setpoint. The drive
will stop when the key is released.
Local/Rem Key Active
1253
Enables the L/R soft key function. This is used to change between Local and Remote sequencing modes from the GKP.
Local Dir Key Active
1255
Enables the ability to change the direction from the GKP when running in local sequencing mode. When FALSE the direction will
always be positive.
Local Run Key Active
1239
Enables the green Run key function when in local sequencing mode. When FALSE the Run key is ignored, (for both RUN and JOG
modes).
Local Reverse
1240
Used to change the direction the motor will rotate when in local sequencing mode. When FALSE the direction will be "Forwards". When
TRUE the direction will be reverse.
AC30 series Variable Speed Drive
Path
Parameters::Keypad::Local Control
Parameters::Keypad::Local Control
Parameters::Keypad::Local Control
Parameters::Keypad::Local Control
Parameters::Keypad::Local Control
Parameter Reference
Default
Range
0
0:RUN
1:JOG
TRUE
TRUE
TRUE
FALSE
D-101
Units
Writable
STOPPED
ALWAYS
ALWAYS
ALWAYS
ALWAYS