Parameter Name
No.
A 32-bit word that can be used to enable, (or disable), individual trips. Bit 0 of this word corresponds to trip 33, up to bit 31 of this word
which corresponds to trip 64.
Refer to Chapter 10 "Trips and Fault Finding" for details of the value corresponding to each trip.
Active 1 - 32
0763
A 32-bit word that indicates which trip sources are active. For example, the HEATSINK OVERTEMP may remain true for some time
after the initial fault is reported.
The Active value shows active trip sources even if the corresponding trip is not enabled in "Enabled 1-32".
Refer to Chapter 10 "Trips and Fault Finding" for details of the value corresponding to each trip.
AC30 series Variable Speed Drive
Path
Monitor::Trips
Parameters::Trips::Trips Status
Parameter Reference
Default
Range
0:01 OVER VOLTAGE
1:02 UNDER VOLTAGE
2:03 OVER CURRENT
3:04 STACK FAULT
4:05 STACK OVER CURRENT
5:06 CURRENT LIMIT
6:07 MOTOR STALL
7:08 INVERSE TIME
8:09 MOTOR I2T
9:10 LOW SPEED I
10:11 HEATSINK OVERTEMP
11:12 INTERNAL OVERTEMP
12:13 MOTOR OVERTEMP
13:14 EXTERNAL TRIP
14:15 BRAKE SHORT CCT
15:16 BRAKE RESISTOR
16:17 BRAKE SWITCH
17:18 LOCAL CONTROL
18:19 COMMS BREAK
19:20 LINE CONTACTOR
20:21 PHASE FAIL
21:22 VDC RIPPLE
22:23 BASE MODBUS BREAK
23:24 24 V OVERLOAD
24:25 PMAC SPEED ERROR
25:26 OVERSPEED
26:27 STO ACTIVE
27:28 FEEDBACK MISSING
28:29 INTERNAL FAN FAIL
29:30 CURRENT SENSOR
30:31 POWER LOSS STOP
31:32 SPEED SENSOR
D-203
Units
Writable
NEVER