Parker AC30 Série Mode D'emploi page 487

Masquer les pouces Voir aussi pour AC30 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Trips Status
Parameters::Trips::Trips Status
Parameter Name
No.
0696
First Trip
An enumerated value that shows the trip that caused the AC30 to disable the stack. When multiple trips are active at the same time,
(for example Over Current followed by Over Temperature), this parameters shows the first trip that the AC30 detected. Refer to
Chapter 10 "Trips and Fault Finding", for details of each trip source.
AC30 series Variable Speed Drive
Path
Monitor::Trips
Parameters::Trips::Trips Status
Parameter Reference
Default
Range
0:NONE
1:01 OVER VOLTAGE
2:02 UNDER VOLTAGE
3:03 OVER CURRENT
4:04 STACK FAULT
5:05 STACK OVER CURRENT
6:06 CURRENT LIMIT
7:07 MOTOR STALL
8:08 INVERSE TIME
9:09 MOTOR I2T
10:10 LOW SPEED I
11:11 HEATSINK OVERTEMP
12:12 INTERNAL OVERTEMP
13:13 MOTOR OVERTEMP
14:14 EXTERNAL TRIP
15:15 BRAKE SHORT CCT
16:16 BRAKE RESISTOR
17:17 BRAKE SWITCH
18:18 LOCAL CONTROL
19:19 COMMS BREAK
20:20 LINE CONTACTOR
21:21 PHASE FAIL
22:22 VDC RIPPLE
23:23 BASE MODBUS BREAK
24:24 24 V OVERLOAD
25:25 PMAC SPEED ERROR
26:26 OVERSPEED
27:27 STO ACTIVE
28:28 FEEDBACK MISSING
29:29 INTERNAL FAN FAIL
30:30 CURRENT SENSOR
31:31 POWER LOSS STOP
32:32 SPEED SENSOR
33:33 A1
34:34 A2
35:35 A3
36:36 A4
37:37 A5
38:38 A6
39:39 A7
40:40 A8
41:41 SPEED ERROR
42:42 PEERTOPEER OVERRUN
43:43 PHASE CONFIG
44:44 ETHERNET IP BREAK
45:45 RESOLVER ERROR
46:46 PMAC ALIGN ERROR
47:47 CURRENT IMBALANCE