Parameter Reference
Stack Inv Time
Parameters::Motor Control::Stack Inv Time
The purpose of the inverse time is to automatically reduce the drive current limit in response to prolonged overload conditions.
For a short time given by Short Overload Time, the drive is able to provide the Short Overload Level
For a long time given by Long Overload Time, the drive is able to provide the Long Overload Level
These 2 protections work in parallel, the output limit current is the maximum value if Inv Time Active = False. If Inv Time Active = True, the
current limit is determined by Long Overload Level
the current limit is not yet ramped down. If already ramped down, the current limit is due to the long overload.
When the maximum overload value is reached, the inverse time current limit is ramped down. The rate at which the inverse time current limit is
ramped to the Inv Aiming Point is defined by Inv Time Down Rate. When the overload condition disappears, the inverse time current limit is ramped
up. The rate at which the inverse time current limit is ramped to the maximum value is defined by Inv Time Up Rate.
% Are all referring to drive/stack ratings.
Parameter Name
No.
100% Stk Current
0343
Stack rating in rms amps corresponding to 100% stack current
Long Overload Level
0344
Overload value in % of the stack amps for long overload condition(*)
Long Overload Time
0345
Maximum duration under long overload condition (typically 60s)
Path
Parameters::Motor Control::Stack Inv
Time
Parameters::Motor Control::Stack Inv
Time
Parameters::Motor Control::Stack Inv
Time
Default
Range
x.x
0.0 to 10000.0
x.
0 to 200
0.000 to 100000.000
Units
Writable
NEVER
A
%
NEVER
NEVER
s
AC30 series Variable Speed Drive