D-152
Parameter Reference
Parameter Name
No.
Symmetric Mode
0488
Select whether to use Acceleration Time and Deceleration Time pair of ramp rates, or to use Symmetric Time to define the ramp
rate for the Drive.
Ramp Type
0485
Selects the ramp type
Symmetric Mode
0488
Symmetric Time
0489
The time that the Drive will take to ramp from 0.00% to 100.00% and from 100.00% to 0.00% when Symmetric Mode is TRUE.
Sramp Continuous
0490
When TRUE, and S ramp is selected in Ramp Type, forces a smooth transition if the speed setpoint is changed when ramping. The
curve is controlled by the Sramp Acceleration and Sramp Jerk1 to Sramp Jerk 4 parameters. When FALSE, there is an immediate
transition from the old curve to the new curve.
Sramp Acceleration
0491
Sets the acceleration rate in units of percent per second², i.e. if the full speed of the machine is 1.25m/s then the acceleration will be:
1.25 x 75.00% = 0.9375m/s²
0492
Sramp Deceleration
This functions in the same way as Sramp Acceleration above.
Path
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Parameters::Motor Control::Ramp
Default
Range
FALSE
0
0:LINEAR
1:S RAMP
FALSE
10.000
0.000 to 3000.000
FALSE
10.0
0.0 to 100.0
10.0
0.0 to 100.0
Units
Writable
ALWAYS
ALWAYS
ALWAYS
s
ALWAYS
ALWAYS
%/s²
ALWAYS
%/s²
ALWAYS
AC30 series Variable Speed Drive