D-82
Parameter Reference
Flycatching
Parameters::Motor Control::Flycatching
Only available if IM MOTOR selected in Control Mode
This feature performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the motor to the desired
setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a fan to `windmill'.
Parameter Name
No.
VHz Flying Start Enable
0310
Enable flycatching in V/Hz control mode when TRUE
VC Flying Start Enable
0311
Enable flycatching in Vector control mode when TRUE
Flying Start Mode
0312
Mode of operation - V/Hz control
0313
Search Mode
The type of speed search carried out by the flycatching sequence.
0314
Search Volts
Only under VHz control
The percentage level of the search volts applied to the motor during the speed search phase of the flycatching sequence. Increasing
this parameter improves the accuracy of the discovered motor speed but increases the braking influence of the speed search on the
rotating motor.
Search Boost
0315
Only under VHz control
Path
Parameters::Motor Control::Flycatching
Parameters::Motor Control::Flycatching
Parameters::Motor Control::Flycatching
Parameters::Motor Control::Flycatching
Parameters::Motor Control::Flycatching
Parameters::Motor Control::Flycatching
Default
Range
FALSE
FALSE
0
0:ALWAYS
1:TRIP OR POWER UP
2:TRIP
0
0:BIDIRECTIONAL
1:UNIDIRECTION
9.0
0.0 to 100.0
40.0
0.0 to 50.0
Units
Writable
ALWAYS
ALWAYS
ALWAYS
ALWAYS
%
ALWAYS
ALWAYS
%
AC30 series Variable Speed Drive