Induction Motor Data
Setup::Motor Control::Induction Motor Data
Parameters::Motor Control::Induction Motor Data
Only available if IM MOTOR selected in Control Mode
Parameter Name
No.
Magnetising Current
0568
The no load current of the induction motor, defined as rotor flux / magnetising inductance, usually given the title "imr".
Rotor Time Constant
0569
Induction Motor rotor time constant.
Leakage Inductance
0570
Induction motor leakage inductance. Displayed as star or delta equivalent value according to "Per Phase Parameters" setting.
Stator Resistance
0571
Induction motor stator resistance. Displayed as star or delta equivalent value according to "Per Phase Parameters" setting.
Mutual Inductance
0572
Induction motor mutual inductance. Displayed as star or delta equivalent value according to "Per Phase Parameters" setting.
AC30 series Variable Speed Drive
Path
Parameters::Motor Control::Induction
Motor Data
Parameters::Motor Control::Induction
Motor Data
Parameters::Motor Control::Induction
Motor Data
Parameters::Motor Control::Induction
Motor Data
Parameters::Motor Control::Induction
Motor Data
Parameter Reference
Default
Range
1.00
0.00 to 10000.00
0.100
0.005 to 100.000
1.000
0.000 to 1000.000
0.0000
0.0000 to 100.0000
100.00
0.00 to 10000.00
D-89
Units
Writable
A
ALWAYS
ALWAYS
s
mH
ALWAYS
ALWAYS
Ohm
mH