TROUBLESHOOTING AND TIPS

The inverter fails to come out of configuration mode
The input or output mapping tables have invalid parameter mappings. The parameter 3130 EtherNet IP State will report ERROR. Check the
parameter 3131 EtherNet IP Diag to determine which mapping table has the incorrect mapping. Note the input mapping table may only contain
read-writable parameters.
Failure to make a connection
A connection between scanner and the adapter will not be made if:
the input and output assembly data sizes of the scanner do not match the input and output mapping data sizes of the inverter
the Requested Packet Interval (RPI) of the scanner is set to less than 2ms
Requested Packet Interval (RPI)
When mapping a large amount of data use an RPI of at least 10ms.