A-12
Fieldbuses
INVERTER CONFIGURATION
Enabling
To enable the EtherNet/IP adapter set the parameter 3128 EtherNet IP Enable to TRUE.
The current state of the EtherNet/IP adapter is given by the parameter 3130 EtherNet IP State.
Note the EtherNet/IP adapter is only active when the inverter is in the Operational state.
IP Settings
The IP settings are set up from the inverter using the Ethernet parameters described in Chapter 12. The IP settings of the inverter cannot be set
via the PLC.
The current IP settings are monitored using the parameters:
0926 IP Address
0927 Subnet Mask
0928 Gateway Address
If parameter 0929 DHCP is set to TRUE, then the IP address will be set from the DHCP server on the network, if one is available.
If parameter 0930 Auto IP is set to TRUE, then the IP address will be automatically be assigned a link-local address.
If both parameters 0929 DHCP and 0930 Auto IP are FALSE, then the IP address, subnet mask and gateway address will be set from the values
in the parameters:
0933 User IP Address
0934 User Subnet Mask
0935 User Gateway Address