Parker AC30 Série Mode D'emploi page 318

Masquer les pouces Voir aussi pour AC30 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D-32
Parameter Reference
Parameter Name
No.
Full Restore
1538
If the parameter 1537 Clone Direction is set to LOAD FROM FILE, then the parameter Full Restore determines if a full restore or a
partial restore is required from the file specified.
If YES is chosen then all the saved parameters and the saved application will be loaded including 'drive unique' parameters.
If PARTIAL is chosen then the user has the choice of what to restore, however 'drive unique' parameters will keep their current values.
The following clone parameters apply:
1539 Application
1541 Power Parameters
1540 Other parameters
Notes:
If the power stack of the drive is different to the power stack from which the clone file was saved and the user chooses YES then the
clone load will not be permitted. However the clone load will be permitted if the control module on which the user is restoring is not
attached to a power stack, or if PARTIAL is chosen instead.
The power parameters cannot be restored from a clone file that was saved on a control module with the parameter 0989 Power Stack
Required set to NONE.
Application
1539
If the parameter 1538 Full Restore is set to PARTIAL, then the parameter Application allows the user to either load the application
from the file or to leave the currently installed application.
Power Parameters
1541
If the parameter 1538 Full Restore is set to PARTIAL, then the parameter Power Parameters allows the user to load the 'power'
parameters from the file, leave the current values or set the values to the defaults.
Notes:
If the power stack of the drive is different to the power stack from which the clone file was saved and the user chooses LOAD FROM
FILE then the clone load will not be permitted. However the clone load will be permitted if the control module on which the user is
restoring is not attached to a power stack, or if LEAVE CURRENT VALUES or SET TO DEFAULT VALUES is chosen instead.
Path
Same as PNO 1534
Same as PNO 1534
Same as PNO 1534
Default
Range
0
0:YES
1:PARTIAL
0
0:LOAD FROM FILE
1:LEAVE CURRENT APP
0
Same as PNO 1540
Units
Writable
ALWAYS
ALWAYS
ALWAYS
AC30 series Variable Speed Drive

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ac30pAc30dAc30v

Table des Matières