D-106
Parameter Reference
Motor Load
Parameters::Motor Control::Motor Load
Motor Protection, function of the motor type.
The Motor Load parameters determines the allowed level of motor overload. This can be especially useful when operating with motors smaller than
the drive rating.
For an IM, an IxT protection is used and provides a current reduction if the max overload level is reached.
The max overload level is calculated based on a 150% for 60s.
For a PMAC motor, the motor load is calculated using the rated motor current and the thermal time constant (2 parameters of the PMAC motor
module). The Thermal time constant is used as the constant time of a simple 1
% Are all related to rated motor current.
Parameter Name
No.
100% Mot Current
0332
Motor current in Amps rms corresponding to 100%
Mot Inv Time Overload
0333
Only available for IM motor
Overload % of the motor inverse time protection
Mot Inv Time Delay
0334
Only available for IM motor
Overload time of the motor inverse time protection from cold state
Path
Parameters::Motor Control::Motor Load
Parameters::Motor Control::Motor Load
Parameters::Motor Control::Motor Load
st
order low pass filter.
Default
Range
x.x
0.0 to 10000.0
x.
0 to 500
6.000 to 60.000
Units
Writable
NEVER
NEVER
%
s
ALWAYS
AC30 series Variable Speed Drive