Parker AC30 Série Mode D'emploi page 346

Masquer les pouces Voir aussi pour AC30 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D-60
Parameter Reference
Encoder Slot 1
Parameters::System Board::Encoder Slot 1
This feature allows you to setup and monitor the operation of the encoder attached to slot 1 of the system board.
Parameter Name
No.
1663
Encoder Supply
Configures the encoder supply for both Encoder 1 and Encoder 2
1664
Encoder Lines
The number of lines per encoder revolution
1665
Encoder Invert
Reverses the encoder direction if TRUE.
1666
Encoder Type
Normally the encoder will be quadrature. Exceptionally, eg if a proximity sensor or other pulse train is used, it needs to be clock /
direction.
1667
High Input Threshold
Changes the threshold level for the encoder pulses between 1.8 V and 6.5 V typical. For encoders powered from 5 V the low theshold
should be used. For other supply voltages the high threshold will provide greater noise immunity.
1668
Encoder Speed
The speed measured by the encoder, in revolutions per minute.
Path
Setup::Inputs and Outputs::SB Encoder
Slot1
Parameters::System Board::Encoder
Slot 1
Same as PNO 1663
Same as PNO 1663
Same as PNO 1663
Same as PNO 1663
Monitor::System Board::Encoder Slot 1
Parameters::System Board::Encoder Slot 1
Default
Range
0
0:5 V
1:12 V
2:15 V
3:20 V
2048
1 to 100000
FALSE
0
0:QUADRATURE
1:CLOCK/DIRECTION
FALSE
Units
Writable
STOPPED
STOPPED
STOPPED
STOPPED
RPM
NEVER
AC30 series Variable Speed Drive

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ac30pAc30dAc30v

Table des Matières