D-58
Parameter Reference
Encoder
Setup::Inputs and Outputs::Option
Monitor::Inputs and Outputs
Parameters::Option IO::Encoder
This feature allows you to setup and monitor the operation of the Encoder.
Parameter Name
No.
Encoder Supply
1511
Allows the user to select the correct supply voltage for the pulse encoder.
Encoder Lines
1512
The number of lines per one encoder revolution, as required by the encoder in use. Incorrect setting of this parameter will result in an
erroneous speed measurement.
Encoder Invert
1513
Reverses the encoder direction if set to TRUE. The encoder direction needs to be correct if encoder feedback is used to control the
motor in vector mode. The autotune identifies whether the parameter is in the correct state required to control the motor, and changes
it if necessary. It is possible to do this manually, by attempting to run the motor, and changing the parameter if necessary until the
motor is controlled correctly.
Encoder Type
1514
Normally the encoder type will be quadrature. Exceptionally, e.g. if a proximity sensor or other pulse train is used, it needs to be clock /
direction type.
Encoder Single Ended
1515
Path
Setup::Inputs and Outputs::Option
Parameters::Option IO::Encoder
Same as PNO 1511
Same as PNO 1511
Same as PNO 1511
Same as PNO 1511
Default
Range
0
0:5 V
1:12 V
2:15 V
3:24 V
2048
1 to 100000
FALSE
0
0:QUADRATURE
1:CLOCK/DIRECTION
FALSE
Units
Writable
STOPPED
STOPPED
STOPPED
STOPPED
STOPPED
AC30 series Variable Speed Drive