Parker AC30 Série Mode D'emploi page 228

Masquer les pouces Voir aussi pour AC30 Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CIP OBJECTS
The following CIP objects are supported:
01h
Identity
02h
Message Router
04h
Assembly
06h
Connection Manager
64h
Vendor Specific
F5h
TCP/IP Interface
F6h
Ethernet Link
Class Attributes
Each object has the following class attributes.
Attribute
Description
1
Revision
2
Maximum Instance
3
Number of Instances
4
Optional Attribute List
5
Optional Service List
6
Maximum Class Attribute
7
Maximum Instance Attribute
Supported Service Code
0Eh
Identity Object – 01h
Instance
Attribute
1
1
2
3
4
5
6
7
Supported Service Code
01h
05h
0Eh
1.
Both Type 0 and Type 1 Reset will restart DHCP if enabled.
AC30 series Variable Speed Inverter
Type
UINT
UINT
UINT
UINT
UINT
UINT
UINT
Service Name
Get_Attribute_Single
Description
Type
Vendor
UINT
Device Type
UINT
Product Code
UINT
Product Revision
UINT
Status
WORD
Serial Number
UDINT
Product Name
SHORT STRING
Service Name
Get_Attribute_All
Reset - Type 0 and Type 1 Reset are supported
Get_Attribute_Single
Access
Get
Get
Get
Get
Get
Get
Get
Value
0004h (Parker Hannifin)
002Bh (Generic)
306
02C02h (minor/major)
0
Last 4 bytes of inverter MAC address
"Parker AC30 Drive"
1
A-26
Fieldbuses
Access
Get
Get
Get
Get
Get
Get
Get

Publicité