12-23
Ethernet
Parameter Name
3: DISABLED
4: LISTENING
5: PRE-MASTER
6: MASTER
7: PASSIVE
8: UNCALIBRATED
9: SLAVE
PTP Clock
PTP parameter.
Diagnostic parameter giving the current value of the PTP clock to 1 second accuracy. Note this is not intended to represent the
actual date and time.
PTP Offset
PTP parameter.
Diagnostic parameter giving the average offset in nanoseconds between the PTP clock and the master clock.
PTP Locked
PTP parameter.
Diagnostic parameter indicating when the inverter is a slave that the PTP clock has synchronised to a master clock determined by
parameter 1685 PTP Locked Threshold. If the inverter is a master then this parameter will be set to TRUE.
No.
Path
- the PTP will not send any messages and will accept only PTP management messages
- the PTP is listening for Announce messages from a master or waiting to timeout on received announce
messages.
- the PTP behaves as though it were in the MASTER state but will not send any messages except for
peer delay, signalling or management messages.
- the PTP is behaving as a master
- the PTP will not send any messages except for peer delay, signalling or management messages
- the PTP is in a transient state. One or more master ports have been detected in the domain. The
appropriate master port has been selected, and the local port is preparing to synchronize to the selected
master port.
- the PTP is synchronizing or synchronized to a master
1699
Monitor::Communications::PTP
Parameters::Base Comms::PTP
1687
Monitor::Communications::PTP
Parameters::Base Comms::PTP
1688
Monitor::Communications::PTP
Parameters::Base Comms::PTP
Default
Range
1970/01/01 00:00:00
-
0 ns
-2000000000 to
2000000000
FALSE
FALSE
TRUE
Units
Writable
NEVER
NEVER
NEVER
AC30 series Variable Speed Inverters