NOTICE
The configuration of the hydraulics must be carried out before establishing the twin-head
pump connection. With twin-head pumps delivered from the factory, the hydraulic position
is pre-configured.
10.3
Display for twin-head pump operation
Two pump symbols are displayed in twin-head pump operation in the "Active influences" area. This is what
they mean:
•
The left symbol represents the pump being viewed.
•
The right-hand symbol represents the partner pump.
The indication of the symbols in the display differs for generic twin-head pump and two-pump system in-
stalled with two single pumps in the Y-piece:
Generic twin-head pump
On the twin-head pump, the left drive is equipped with a graphic display and the right drive with an LED dis-
play.
The graphic display of the main pump shows the values and settings.
On the graphic display, the home screen is visible as with a single pump.
Nothing is shown on the LED display of the partner pump.
Illustration of the pump symbols and meaning:
Display of
main pump
Case 1
Case 2:
Case 3:
Case 4
Case 5
Case 6
Two single pumps as two-pump system in Y-piece joint
If two single pumps are operated as a two-pump system in a Y-piece system, each pump has a graphic dis-
play showing values and settings.
NOTICE
The displayed actual values shown on the display of the pump drive, which is not in opera-
tion, correspond 1:1 to the values of the active drive.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Display of
partner pump
Description
Main/standby operation: Only the main pump is
running.
Main/standby operation: Only the partner pump is
running.
Parallel operation: Only the main pump is running.
Parallel operation: Only the partner pump is run-
ning.
Parallel operation: The main pump and partner
pump are running.
Main/standby operation or parallel operation: No
pump running.
en-US