4
Intended use and misuse
4.1
Intended use
Pumps for heating/air conditioning/cooling applications
CAUTION
Damage to pump possible!
Prohibited fluids will destroy the pumps!
This pump is only designed for use with water and water/glycol.
Stratos MAXO/-D series smart-pumps are intended to circulate fluids in the following application areas:
Hot water heating systems
Cooling and cold water circuits
Closed industrial circulation systems
Solar installations
Geothermal systems
Air-conditioning systems
The pumps do not meet the requirements of the ATEX directive and are not suitable for pumping explo-
sive or highly flammable fluids!
Proper intended use also includes compliance with these instructions in addition to the information and la-
bels on the pump.
Any other use is regarded as improper use and results in the loss of all liability claims.
Approved fluids
Heating pumps:
Heating water in accordance with VDI 2035 part 1 and part 2
Demineralized water in accordance with VDI 2035-2, "Water quality" section
Water-glycol mixture, max. mixing ratio 1:1
If glycol is added, the pumping data of the pump must be corrected according to the higher viscosity, de-
pending on the mixing ratio percentage.
Ethylene/propylene glycols with corrosion protection inhibitors.
No oxygen binding agents, no chemical sealants (ensure system is closed in terms of corrosion according
to VDI 2035); fix leaky spots.
Standard commercial corrosion protection inhibitors
due to consumption!).
Standard commercial corrosion protection inhibitors
Standard commercial cooling brines
WARNING
Injuries to people and property damage caused by unauthorized fluids!
Unauthorized fluids can cause injuries to people and can destroy the pump.
• Only use branded goods with corrosion prevention inhibitors!
• Observe chloride content of filling-up water in accordance with manufacturer's specifi-
cations! Soldering pastes containing chloride are not permitted!
• Safety data sheets and manufacturers' specifications must be observed!
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
1)
without corrosive anodic inhibitors (under-dosing
1)
without inorganic or polymer filming agents.
1)
.
en-US