Minimum signal/value assignment
Analog input (AI2)
Signal value
Corresponding value
Fig. 62: Minimum signal/value assignment, actual value sensor
The value for the minimum signal describes the lower signal value of the transmission ramp with an associ-
ated value of 0%. This is the equivalent of 0.0 mA for 14 °F (-10 °C) in this example.
Max. signal/value assignment
Analog input (AI2)
Signal value
Corresponding value
Fig. 63: Maximum signal/value assignment, actual value sensor
Data input is complete once the minimum and maximum characteristic curve support points have been en-
tered.
The value for the maximum signal describes the upper signal value of the transmission ramp with an associ-
ated value of 100%. This is the equivalent of 20.0 mA for 248 °F (120 °C) in this example
120
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Set minimum point
of actual value
pump curve for
temperature sensor.
Set maximum point
of actual value
pump curve for
temperature sensor.