Settings menu
Q-Limit
Max
Visible for active control modes, which support ad-
ditional control function "Q-Limit
fined applications in the settings assistant [" 79]"
table).
Q-Limit
Min
Visible for active control modes, which support the
additional control function "Q-Limit
defined applications in the settings assistant" [" 79]
table).
Disinfection detection
Visible for active control modes, which support the
additional control function "Detection of disinfec-
tion". (see "Pre-defined applications in the settings
assistant" [" 79] table).
Emergency operation speed
Visible for active control modes that reset to a fixed
speed.
PID parameter Kp
Visible for user-defined PID control.
PID parameter: Ki
Visible for user-defined PID control.
PID parameter Kd
Visible for user-defined PID control.
PID: Inversion
Visible for user-defined PID control.
Pump On/Off
Always visible.
Table 23: Settings menu - Set control mode
Example: "Multi-Flow Adaptation" via "Hydraulic shunt" system type
Set control mode
Select the "Hydraulic shunt" system type by turning the operating button on the feeder pump and press to
confirm.
For the "Hydraulic shunt" system type in the "Heating" application, select and confirm the control mode
Multi-Flow Adaptation.
Setting assistant – Selection of secondary pumps
Select secondary pumps that have to be supplied downstream of the hydraulic shunt and connect them to
Wilo Net.
Select "Selection of secondary pumps" by turning the operating button and press to confirm. Each partner
pump has to be selected as secondary pump from the pumps detected by Wilo Net.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Description
Setting an upper threshold of the volume flow.
". (see "Pre-de-
Max
Setting a lower threshold of the volume flow.
". (see "Pre-
Min
The pump automatically switches to this constant
speed if the set control mode fails (e.g. sensor signal
fault).
Setting the Kp factor for the user-defined PID con-
trol.
Setting the Ki factor for the user-defined PID con-
trol.
Setting the Kd factor for the user-defined PID con-
trol.
Setting the inversion for the user-defined PID con-
trol.
Switching the pump on/off with low priority. A MAX,
MIN, MANUAL override switches the pump on.
en-US
87