en-US
Code
Error
601
Setpoint source not suitably
configured.
The setpoint source is not correctly configured. In the context menu there is a link for configur-
ing the setpoint source.
602
Setpoint source not available.
The setpoint source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
603
Sensor source not suitably
configured.
The sensor source is not correctly configured. In the context menu there is a link for configuring
the sensor source.
604
Same sensor source not possi-
ble.
The sensor sources are not correctly configured. In the context menu there is a link for configur-
ing the sensor sources.
606
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
607
Sensor source not suitably
configured.
The sensor source is not correctly configured. In the context menu there is a link for configuring
the sensor source.
609
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
610
Sensor source not suitably
configured.
The sensor source is not correctly configured. In the context menu there is a link for configuring
the sensor source.
611
Same sensor source not possi-
ble.
The sensor sources are not correctly configured. In the context menu there is a link for configur-
ing the sensor sources.
154
Cause
Setpoint is not connected
to correct source. Input not
suitably configured.
Setpoint not connected to
existing CIF module.
Sensor 1 is not connected
to correct source. Input not
suitably configured.
Sensor sources are config-
ured to the same source.
Sensor value 1 is not con-
nected to existing CIF
module.
Sensor 2 is not connected
to correct source. Input not
suitably configured.
Sensor value 2 is not con-
nected to existing CIF
module.
Feed temperature sensor is
not connected to correct
source. Input not suitably
configured.
Sensor sources for heat
meter configured for the
same source.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Remedy
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source.
Select other source.
Configure a sensor source to an-
other source.
Insert CIF module.
Activate CIF module.
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
Configure source to "temperature
sensor" usage type or select an-
other source.
Configure one of the sensor
sources for the heat meter to an-
other source.