en-US
Then configure the sensor source and sensor position in the "Sensor feed temperature" and "Sensor return
temperature" menu items.
Configuring the sensor source in the feed
In the "Diagnostics and measured values" menu
1.
"Heating/cooling quantity measurement"
2.
"Sensor feed temperature"
3.
Select "Select sensor source".
Configuring the sensor source in the return
In the "Diagnostics and measured values" menu
1.
"Heating/cooling quantity measurement"
2.
"Sensor return temperature"
3.
Select "Select sensor source".
Potential sensor source options:
•
Internal sensor
•
Analog input (AI1)
•
Analog input (AI2)
•
CIF module
Configuring the sensor position in the feed
1.
"Heating/cooling quantity measurement"
2.
"Sensor feed temperature"
3.
Select "Select sensor position".
Select "Internal sensor", "Feed" or "Return" as the sensor positions.
Configuring the sensor position in the return
1.
"Heating/cooling quantity measurement"
2.
"Sensor return temperature"
3.
Select "Select sensor position".
Select "Internal sensor", "Feed" or "Return" as the sensor positions.
Potential sensor position options:
•
Internal sensor
•
Analog input (AI1)
•
Analog input (AI2)
•
BMS (Building management systems)
•
Feed
•
Return
•
Primary loop 1
•
Primary loop 2
•
Secondary loop 1
•
Secondary loop 2
•
Accumulator
•
Hall
128
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10