If the signal type PT1000 was selected, it is possible to set a temperature correction value
for the measured temperature. With this the electrical resistance of a long sensor cable can
be compensated.
In the "Settings" menu 
1.
"External interfaces"
2.
"Function analog input AI1" or "Function analog input AI2"
3.
"Temperature correction" and set correction value (offset).
NOTICE
Optionally specify the position of the sensor for better understanding of the connected sen-
sor's function.
This configured position does not influence the function or sensor use.
In the "Settings" menu 
1.
"External interfaces"
2.
"Function analog input AI1" or "Function analog input AI2"
3.
"Select the sensor position".
The following positions are available:
Internal sensor
Analog input 1
Analog input 2
BMS (Building management systems)
Feed
Return
Primary loop 1
Primary loop 2
Secondary loop 1
Secondary loop 2
Accumulator
Hall
Circulation
11.6
Application and function of the Wilo Net interface
Wilo Net is a bus system which enables up to 21 Wilo products (participants) to communicate with one an-
other.
The Wilo-Smart Gateway counts as a participant.
Application for:
Generic twin-head pump
Two-pump systems consisting of two single pumps (Y-pipe installation)
Multi-Flow Adaptation (feeder pump connected to secondary pumps)
remote access via Wilo-Smart Gateway