en-US
Code
Error
403
Overvoltage
Additional information about causes and remedy:
Operation cannot be maintained. Possible causes:
1. Pump is connected to the wrong power supply
2. Three-phase power supply is unsymmetrically loaded by
unevenly connected single-phase consumers.
404
Pump blocked.
Additional information about causes and remedy:
In addition to deposits and foreign bodies in the system, the pump shaft can also be tilted and
blocked by heavy bearing wear.
405
Electronic module too hot.
Additional information about causes and remedy:
Adhere to permissible installation position and minimum distance from insulation and system
components to ensure sufficient ventilation.
406
Motor too hot.
Additional information about causes and remedy:
Adhere to permissible installation position and minimum distance from insulation and system
components to ensure sufficient ventilation.
407
Connection between motor
and module interrupted.
Additional information about causes and remedies:
Dismantle the electronic module to check the contacts between module and motor.
408
There is flow through the
pump in the opposite direction
of flow.
Additional information about causes and remedy:
If flow passing through pump in the opposite direction is too strong, the motor can no longer
start.
409
Incomplete software update.
Additional information about causes and remedy:
The pump can work only once the software update has been completed.
148
Cause
Power supply is too high.
Mechanical influence is in-
hibiting the rotation of the
pump shaft.
Permissible temperature of
the electronic module is
exceeded.
Permissible motor temper-
ature is exceeded.
Electrical connection be-
tween motor and module
faulty.
External influences cause
flow against the direction
of the pump's flow.
The software update was
not completed.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Remedy
Check power supply.
Check free movement of rotating
parts in the pump head and mo-
tor.
Remove deposits and foreign
substances.
Ensure permissible ambient tem-
perature.
Improve room ventilation.
Ensure permissible ambient and
fluid temperature.
Ensure motor cooling with unob-
structed air circulation.
Check the motor module connec-
tion.
Check power control of the
pumps,
install swing check valve if
needed.
Software update with a new soft-
ware bundle is required.