The analog inputs can be used for the following functions:
External setpoint specification
Sensor connection:
Temperature sensor
Differential pressure sensor
PID sensor
Analog input for following signals:
0 – 10 V
2 – 10 V
0 – 20 mA
4 – 20 mA
PT1000
Technical data:
Load analog input (0)4 – 20 mA: ≤ 300 Ω
Load resistance at 0 – 10 V, 2 – 10 V: ≥ 10 kΩ
Dielectric strength: 30 V DC / 24 V AC
Terminal for supplying active sensors with 24 V DC – maximum power load: 50 mA
NOTICE
For additional information, see section "Application and function of the analog inputs AI1
and AI2 [" 104]"
CAUTION
Overload or short-circuit
In case of overload or short-circuit of the 24 V connection, all input functions will fail (analog
inputs and digital inputs).
The input functions will be available again when the overload or short-circuit situation is re-
solved.
CAUTION
Overvoltages destroy the electronics
Analog and digital inputs are protected for overvoltages up to 30 V DC / 24 V AC. Higher
overvoltages destroy the electronics.
42
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10