both sides. For optimum transmission, the data cable pair (H and L) must be twisted at Wilo Net and have a
characteristic impedance of 120 ohms. Cable length maximum 656 ft.
NOTICE
For additional information, see section "Application and function of the Wilo Net interface
[" 121]".
7.9
Collective fault signal (SSM) – red terminal block
An integrated collective fault signal is available at the SSM (FAULT) terminal as a potential-free changeover
contact.
Contact load:
•
Minimum permissible: SELV 12 V AC / DC, 10 mA
•
Maximum permissible: 250 V AC, 1 A, AC1 / 30 V DC, 1 A
NOTICE
For additional information, see "Application and function of SSM relay [" 97]" section.
7.10
Collective run signal (SBM) – orange terminal block
An integrated collective run signal is available at the SBM (RUN) terminals as a potential-free normally open
contact.
Contact load:
•
Minimum permissible: SELV 12 V AC / DC, 10 mA
•
Maximum permissible: 250 V AC, 1 A, AC1 / 30 V DC, 1 A
NOTICE
For additional information, see "Application and function of SBM relay [" 98]" section.
7.11
CIF module
DANGER
Risk of fatal injury from electric shock!
Immediate danger of death if live components are touched!
• Check whether all connections are voltage-free!
CIF modules (accessories) are used for communication between pumps and building management systems.
CIF modules are attached in the electronic module.
•
For twin-head pumps, only the main pump must be equipped with a CIF module.
•
For pumps in Y-pipe applications in which the electronic modules are connected to each other through the
Wilo Net, only the main pump also requires a CIF module.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10