Télécharger Imprimer la page

Wilo Stratos MAXO Notice De Montage Et De Mise En Service page 156

Publicité

Les langues disponibles

Les langues disponibles

en-US
Code
Error
644
Same sensor source not possi-
ble.
The sensor sources for the cooling function are not correctly configured. In the context menu
there is a link for configuring the sensor sources.
646
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
647
Sensor source not suitably
configured.
The sensor source for the cooling function is not correctly configured. In the context menu there
is a link for configuring the sensor source.
649
Sensor source not available.
The sensor source or the CIF module is not correctly configured. In the context menu there are
links for configuration.
1)
650
No MFA
partner pump
1)
MFA
collects the requirement of configured partner pumps to supply in total. For this purpose,
the partner pumps must be selected in the MFA
Table 53: Configuration warnings
1)
MFA= Multi-Flow Adaptation
17
Spare parts
Original spare parts may only be obtained from local installers and/or Wilo customer service. To avoid queries
and order errors, please provide all data on the rating plate with every order.
18
Disposal
18.1
Information on the collection of used electrical and electronic products
Proper disposal and appropriate recycling of this product prevent damage to the environment and danger to
your personal health.
NOTICE
Do not dispose of in domestic waste!
In the European Union, this symbol may have been included on the product, the packaging,
or the accompanying documentation. It means that the electrical and electronic products in
question must not be disposed of along with domestic waste.
156
Cause
Sensor sources are config-
ured to the same source.
Sensor value is not con-
nected to existing CIF
module.
Sensor 2 is not connected
to correct source. Input not
suitably configured.
Sensor value 2 is not con-
nected to existing CIF
module.
MFA
partner pump is config-
ured.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
1)
is selected, but no
1)
configuration.
Remedy
Configure a sensor source to an-
other source.
Insert CIF module.
Activate CIF module.
Configure source or
select another source.
Insert CIF module.
Activate CIF module.
1)
Configuration of MFA
pumps is required or select an-
other control mode.
partner