Max. signal/value assignment
Analog input (AI2)
Signal value
Corresponding value
Fig. 58: Max. signal/value assignment
The value for the maximum signal describes the upper signal value of the transfer ramp with an associated
value of 8 m. In this example, the lower signal value is 10 V.
When all signal/value assignments have been performed, the setting of the analog setpoint source is com-
pleted.
An editor for adjusting the substitute setpoint in the event of a cable break or wrong configuration of the
analog input will open.
...►
Select setpoint source
Current source: Analog input 2
Set setpoint source
Setpoint sensor: 4 – 20 mA
Substitute setpoint in the event of a
cable break
Current: 6.0 m
Fig. 59: Substitute setpoint in the event of a cable break
116
Set input for external setpoint
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Set maximum point
of setpoint pump curve of
delivery head for Δp-v
.
If a
cable break at the
external setpoint source
is detected, this substitute value is
used
as the setpoint.