Télécharger Imprimer la page

Wilo Stratos MAXO Notice De Montage Et De Mise En Service page 28

Publicité

Les langues disponibles

Les langues disponibles

en-US
Tightening torques for motor fixing bolts
Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z
1.25 x 3 – 15; 1.25 x 3 – 20; 1.25 x 3 – 25
1.25 x 3 – 30; 1.25 x 3 – 35; 1.25 x 3 – 52
1.5 x 3 – 52
2 x 3 – 20; 2 x 3 – 25; 2 x 3 – 35
2 x 3 – 50
3 x 3 – 20; 3 x 3 – 40; 3 x 3 – 52
Table 7: Tightening torques
6.6
Insulating
Insulation of the pump in heating systems and domestic hot water circulation applications
Single and twin-head pump housings can be insulated with commercially available insulation materials.
WARNING
Risk of burns from hot surfaces!
The entire pump can become very hot. When retrofitting the insulation during ongoing op-
eration, there is a risk of burns!
• Allow the pump to cool down before any work.
Insulation of the pump in cooling/air-conditioning systems
Single and twin-head pumps can be insulated with commercially available diffusion-tight insulation materi-
als for use in refrigeration and air-conditioning applications.
CAUTION
Electrical defect!
Condensate that accumulates in the motor can cause an electrical defect.
• Insulate the pump housing only up to the separating gap to the motor!
• Keep the condensate drain grooves unobstructed to ensure that condensate that devel-
ops in the motor can drain off unobstructed!
28
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Tightening torques
[inlb]
70.8 ... 88.5
159.3 ... 177

Publicité

loading

Ce manuel est également adapté pour:

Stratos maxo-dStratos maxo-z