Wilo Stratos MAXO Notice De Montage Et De Mise En Service page 101

Publicité

Les langues disponibles

Les langues disponibles

2.
Select "Function control input DI1" or "Function control input DI2".
Possible settings:
Selection option
Not used
External OFF
External MAX
External MIN
1)
External MANUAL
2)
External key lock
Heating/cooling switchover
Table 34: Function control input DI1 or DI2
1)
Function: See section "Adjustment - Manual operation [" 88]".
2)
Function: See "Key lock ON [" 126]" section.
3)
To guarantee the heating/cooling switchover function operates correctly at the digital input:
1.
Go to
"Settings" menu, "Set control mode", "Setting assistant" and select the "Heating & cooling"
application and
2.
go to
"Settings" menu, "Set control mode", "Heating/cooling switchover" and select the "Binary
input" option as switchover criterion.
Procedure with EXT. OFF for twin-head pumps
The function EXT. OFF always behaves as follows:
EXT. OFF active: Contact is open, pump is stopped (OFF).
EXT. OFF inactive: Contact is closed, pump runs in normal operation (ON).
The configuration of the control inputs has three possible modes (from SW ≥ 1.05.10.00) for EXT. OFF which
can influence the behavior of the two twin-head pump partners.
System mode
The control input of the main pump is occupied with a control cable and configured to EXT. OFF.
The control input on the main pump switches both twin-head pump partners.
The control input of the partner pump is ignored and has no significance regardless of its configuration. If
the main pump malfunctions or if the twin-head pump connection is disconnected, the partner pump is also
stopped.
Installation and operating instructions • Wilo-Stratos MAXO/-D/-Z • Ed.02/2023-10
Function control input DI1 or DI2
The control input does not have a function.
Contact open: Pump is switched off.
Contact closed: Pump is switched on.
Contact open: Pump is running in the mode set on the pump.
Contact closed: Pump is running with maximum speed.
Contact open: Pump is running in the mode set on the pump.
Contact closed: Pump is running with minimum speed.
Contact open: Pump is running in the mode set
on the pump or in mode requested via bus communication.
Contact closed: Pump is set to MANUAL.
Contact open: Key lock is deactivated.
Contact closed: Key lock is activated.
3)
Contact open: "Heating" active.
Contact closed: "Cooling" active.
en-US
101